![ABB ACS880-01 Series Firmware Instructions Download Page 209](http://html.mh-extra.com/html/abb/acs880-01-series/acs880-01-series_firmware-instructions_2621209.webp)
Parameters 209
Speed ref safe
Drive generates a warning (
) and sets the
speed to the speed defined by parameter
(or
when frequency reference
is being used).
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
4
(Visible when
)
Specifies the analog input limits to be supervised. See
parameter
.
Note:
The number of active bits in this parameter depends on
the number of inputs on the extension module.
0000 0000b
0000 0000b …
0011 1111b
Activation of analog input supervision.
1 = 1
(Visible when
Selects a drive signal to be connected to digital input/output
DIO3 when parameter
is set to
For the available selections, see parameter
(Visible when
)
Triggers the analog input tuning function, which enables the
use of actual measurements as the minimum and maximum
input values instead of potentially inaccurate estimates.
Apply the minimum or maximum signal to the input and select
the appropriate tuning function.
See also the drawing at parameter
.
No action
Tuning action completed or no action has been requested.
The parameter automatically reverts to this value after any
tuning action.
0
AI1 min tune
The measured value of AI1 is set as the minimum value of
AI1 into parameter
.
1
AI1 max tune
The measured value of AI1 is set as the maximum value of
AI1 into parameter
2
AI2 min tune
The measured value of AI2 is set as the minimum value of
AI2 into parameter
.
3
AI2 max tune
The measured value of AI2 is set as the maximum value of
AI2 into parameter
4
AI3 min tune
(Visible when
)
The measured value of AI3 is set as the minimum value of
AI3 into parameter
.
5
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
AI1 < MIN
1 = Minimum limit supervision of AI1 active.
1
AI1 > MAX
1 = Maximum limit supervision of AI1 active.
2
AI2 < MIN
1 = Minimum limit supervision of AI2 active.
3
AI2 > MAX
1 = Maximum limit supervision of AI2 active.
4
AI3 < MIN
1 = Minimum limit supervision of AI3 active (FIO-11 only).
5
AI3 > MAX
1 = Maximum limit supervision of AI3 active (FIO-11 only).
6…15
Reserved
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...