364 Parameters
Actual power that the motor absorbs when connected direct-
on-line and operating the application. The value is used for
reference when energy savings are calculated.
Note:
The accuracy of the energy savings calculation is
directly dependent on the accuracy of this value. If nothing is
entered here, then the nominal motor power is used by the
calculation, but that may inflate the energy savings reported
as many motors do not absorb nameplate power.
0.0 kW
0.0 … 100000.0 kW Motor power.
See par.
Resets the savings counter parameters
…
Done
Reset not requested (normal operation), or reset complete.
0
Reset
Reset the savings counter parameters. The value reverts
automatically to
.
1
46
46 Monitoring/scaling
settings
Speed supervision settings; actual signal filtering; general
scaling settings.
Defines the maximum speed value used to define the
acceleration ramp rate and the initial speed value used to
define the deceleration ramp rate (see parameter group
). The speed acceleration and
deceleration ramp times are therefore related to this value
(
not
Also defines the 16-bit scaling of speed-related parameters.
The value of this parameter corresponds to 20000 in fieldbus,
master/follower etc. communication.
1500.00 rpm;
1800.00 rpm
(
0.10 … 30000.00
rpm
Acceleration/deceleration terminal/initial speed.
1 = 1 rpm
Defines the maximum frequency value used to define the
acceleration ramp rate and the initial frequency value used to
define deceleration ramp rate (see parameter group
). The frequency acceleration and
deceleration ramp times are therefore related to this value
(
not
Also defines the 16-bit scaling of frequency-related
parameters. The value of this parameter corresponds to
20000 in fieldbus, master/follower etc. communication.
50.00 Hz;
60.00 Hz
(
0.10 … 1000.00 Hz Acceleration/deceleration terminal/initial frequency.
10 = 1 Hz
Defines the 16-bit scaling of torque parameters. The value of
this parameter (in percent of nominal motor torque)
corresponds to 10000 in fieldbus, master/follower etc.
communication.
See also parameter
100.0%
0.1 … 1000.0%
Torque corresponding to 10000 on fieldbus.
10 = 1%
Defines the output power value that corresponds to 10000 in
fieldbus, master/follower etc. communication. The unit is
selected by parameter
.
1000.00 kW
or hp
0.10 … 30000.00
kW or
0.10 … 40214.48
hp
Power corresponding to 10000 on fieldbus.
1 = 1 unit
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...