312 Parameters
(Only visible when IGBT supply unit control activated by
Selects how the supply unit reacts when an earth fault or
current unbalance is detected.
No action
No action taken.
0
Warning
The supply unit generates an AE02 Earth leakage warning.
1
Fault
The supply unit trips on fault 2E01 Earth leakage.
2
(Only visible when IGBT supply unit control activated by
Selects how the supply unit reacts when a supply phase loss
is detected.
No action
No action taken.
0
Fault
The supply unit trips on fault 3E00 Input phase loss.
1
32
Configuration of signal supervision functions 1…3.
Three values can be chosen to be monitored; a warning or
fault is generated whenever predefined limits are exceeded.
See also section
(page
).
Signal supervision status word.
Indicates whether the values monitored by the signal
supervision functions are within or outside their respective
limits.
Note:
This word is independent of the drive actions defined
.
0000b
0000…0111b
Signal supervision status word.
1 = 1
Selects the mode of signal supervision function 1. Determines
how the monitored signal (see parameter
) is compared
to its lower and upper limits (
respectively).
The action to be taken when the condition is fulfilled is
selected by
Disabled
Signal supervision 1 not in use.
0
Low
Action is taken whenever the signal falls below its lower limit. 1
High
Action is taken whenever the signal rises above its upper
limit.
2
Abs low
Action is taken whenever the absolute value of the signal falls
below its (absolute) lower limit.
3
Abs high
Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
4
Both
Action is taken whenever the signal falls below its low limit or
rises above its high limit.
5
Abs both
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
6
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Supervision 1 active
is outside its limits.
1
Supervision 2 active
is outside its limits.
2
Supervision 3 active
is outside its limits.
3…15
Reserved
Summary of Contents for ACS880-01 Series
Page 1: ...ABB industrial drives Firmware manual ACS880 ESP control program option N5600 ...
Page 4: ......
Page 12: ...12 Table of contents ...
Page 20: ...20 Introduction to the manual ...
Page 22: ...22 Using the control panel ...
Page 28: ...28 Control locations and operating modes ...
Page 146: ...146 Application macros ...
Page 502: ...502 Parameters ...
Page 606: ...606 Fault tracing ...
Page 662: ...662 Control chain diagrams ...