Appendix A Runtime Templates
PID Controller FCM
3BUR002418-600 A
237
SETPT VALUE ON FAIL Field
This field specifies the setpoint value in effect upon a remote link failure. Valid
entry is a value in engineering units.
CHANGE SETPT ON FAIL Field
This field specifies whether a new setpoint value is supplied upon a remote link
failure. Valid entries are:
NO
do not change setpoint
YES
change setpoint
OUTPUT RETURN MODE Field
This field specifies the output mode to enter when the mode returns from Track.
Valid entries are:
PREVIOUS go to the mode active before the output began tracking
MANUAL go to the Manual mode
AUTO
go to the Auto mode
OUTPUT MODE ON FAIL Field
This field specifies the output mode to enter upon a remote link failure. Valid entries
are:
PREVIOUS go to the mode active before the remote link failure
MANUAL go to the Manual mode
AUTO
go to the Auto mode
NO CHANGE remain in the present mode
OUTPUT VALUE ON FAIL Field
This field specifies the output value effective upon a remote link failure if the entry
in the CHANGE OUTPT ON FAIL field is YES. Valid entry is a value in percent.
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......