Appendix A Runtime Templates
AO810, AO890
3BUR002418-600 A
295
PT100
, that will be connected to channel 8. The type
LINEAR
is used if the input is
a -25mV to 75mV signal.
The valid values are:
B, C, E, J, K, N, R, S, T, PT100 and LINEAR
The default entry is J.
TEMPERATURE UNIT
Enter the temperature’s unit of measure; either Centigrade or Fahrenheit.
The valid values are:
C and F
The default value is C.
VALUE CYCLE TIME
Enter the channel value update period (msec) over the fieldbus. Refer to the
S800
I/O User’s Guide
for details of AF 100 loading in relation to cycle time.
The valid values are:
1, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024, 2048 and 4096.
The default value is 128.
AO810, AO890
The S800 I/O AO810 Analog Output Module templet is also used for the AO890
except as noted in the field entry descriptions.
ACTIVE 01 through 08
If the channel is to be active enter a
YES
. If the channel will not be used enter a
NO
.
The default value is YES.
AUTO DOWNLOAD
To automatically download the configuration to the I/O module enter a
YES
. In the
future, if the configuration is to be loaded locally enter a
NO
.
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......