Appendix A Runtime Templates
AO810, AO890
3BUR002418-600 A
297
The default value is 1024.
OSP VALUE 01 through 08
Enter the channel value in counts to output after an OSP TIMEOUT. If the OSP
HOLD has been selected as the OSP value then this field entry is ignored.
The valid values are:
0 to 28480.
Where 0 = 0 mA and 28480 = 20 mA (Counts per mA = 1424)
The default is 0.
POSITION
Enter a number from 1 to 12 representing the position of the I/O module relative to
the FCI. The I/O module directly next to the FCI is number 1.
Default value is 1.
REPORT FAULTS 01 through 08
If channel faults are to be reported, enter a
YES
; if not enter a
NO
.
The default value is YES.
RESERVED OPTIONS
Used to select I/O module type:
Enter:
0 (zero) for the AO810 Module
274333696 for the AO890 Module
The default value is 0 (zero).
If positions are to be used for spare MTUs, the spares must be in place so the rest
of the I/O modules are numbered correctly. The spare MTU will use a position
number when it is on the ModuleBus.
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......