Appendix A Runtime Templates
Loop Definition Templet
3BUR002418-600 A
217
LO ALARM PRIORITY Field
This field specifies the priority level for the low alarm. Valid entries are: STD
(standard priority), MED (medium priority), HIGH (high priority).
BAD MEASURE ALARMS? Field
This field specifies whether the bad data quality alarm for the measured variable is
enabled. The alarm becomes active whenever the data quality of the measured
variable becomes BAD. Valid entries are: YES (enable the alarm), NO (disable the
alarm).
BAD ALARM PRIORITY Field
This field specifies the priority level for the bad data quality alarm. Valid entries are:
STD (standard priority), MED (medium priority), HIGH (high priority).
ENABLE RATE ALARMS? Field
This field specifies whether the rate alarm for the measured variable is enabled. The
rate alarm becomes active when the measured variable changes by an amount
greater than the specified rate limit from one loop processing scan to the next. Valid
entries are: YES (enable the alarm), NO (disable the alarm).
RATE LIMIT Field
This field defines the rate alarm limit for the measured variable. The alarm becomes
active when the variable changes at a rate greater than the limit. Valid entry is: a
number in engineering units, representing the greatest amount the variable can
change per second.
RATE ALARM PRIORITY Field
This field specifies the priority level for the rate alarm. Valid entries are: STD
(standard priority), MED (medium priority), HIGH (high priority).
Usage of rate alarms could cause inconsistency of display for other alarms on any
given tag. It is recommended to not use rate alarms.
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......