Flow Calculation FCM
Appendix A Runtime Templates
262
3BUR002418-600 A
NEW HIGH RANGE Field
This field specifies high range value of the result. Valid entry is any number.
Flow Calculation FCM
This FCM calculates mass and volume flow rates for liquids and gases. Its primary
input is either a differential pressure measurement or a velocity measurement.
STANDARD TEMP Field
This field specifies the standard temperature. Temperature must be absolute
(degrees Rankine). Valid entry is any number.
FLOWING TEMP Field
This field specifies the flow temperature. It is used when TEMP LOC/REM is
LOCAL. The temperature must be absolute (deg. Rankine where deg. Rankine =
deg. Fahr 459.69). Valid entry is any number greater than 0.
FLOWING PRESSURE Field
This field specifies the flow pressure. It is used when PRES LOC/REM is LOCAL.
Valid entry is any number greater than 0. The entry must be in PSIA.
FLOWING DENSITY Field
This field specifies the flow density. It is used when DEN LOC/REM is LOCAL.
Valid entry is any number greater than 0.
DENSITY SC Field
This field specifies the value for the density at standard conditions. Valid entry is
any number.
SPEC GRAV SC Field
This field specifies the value for specific gravity at standard conditions. Valid entry
is any number.
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......