Appendix A Runtime Templates
Adaptive Reset
3BUR002418-600 A
249
ERROR HIGH LIMIT Field
This field specifies the maximum allowed value for the error adaptive contribution
to the overall gain or reset. Valid entry is the high limit value.
ERROR LOW LIMIT Field
This field specifies the minimum allowed value for the error adaptive contribution to
the overall gain or reset. Valid entry is the low limit value.
ERROR UPPER BRKPT Field
This field specifies the upper breakpoint, BP2, for the error adaptive function. The
gain or reset changes when the error becomes greater than the upper breakpoint.
Valid entry is a decimal value in percent.
ERROR LOWER BRKPT Field
This field specifies the lower breakpoint, BP1, for the error adaptive function. The
gain or reset changes when the error becomes less than the lower breakpoint. Valid
entry is a decimal value in percent.
ERROR UPPER FACTOR Field
This field specifies the multiplier of the base gain or reset associated with the upper
breakpoint, BP2, of the error adaptive function. Valid entry is a decimal value.
ERROR LOWER FACTOR Field
This field specifies the multiplier of the base gain or reset associated with the lower
breakpoint, BP1, of the error adaptive function. Valid entry is a decimal value.
Adaptive Reset
The PID Controller FCM uses adaptive gain and/or adaptive reset to adapt to
changing process conditions. This templet is a child of the PID Controller FCM
Templet.
See field description under
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......