PID Controller FCM
Appendix A Runtime Templates
238
3BUR002418-600 A
CHANGE OUTPUT ON FAIL Field
This field specifies if a new output value is supplied upon a remote link failure.
Valid entries are:
NO
do not change the output value
YES
change the output value
LINK TIME-OUT Field
This field specifies the initial time interval for the watchdog timer. The timer is used
to determine whether a supervisory program can continue to control the loop. Valid
entry is a number of seconds
BALANCE MODE Field
This field indicates whether the system can manipulate the remote setpoint ratio
and/or the remote setpoint bias to prevent process bumps when the setpoint state is
switched to remote. Valid entries are:
RATIO
FCM automatically manipulates ratio value of remote setpoint to
balance transitions to Remote
BIAS
controller automatically manipulates bias value of remote setpoint
to balance transitions to Remote
BOTH
the system can manipulate both bias and ratio
OFF
the balance feature is not used
BIAS MODE Field
This field specifies which remote setpoint bias value the FCM is presently using.
The configured entry is the initial bias mode. During runtime, this field changes
each time the mode is switched at the console. Valid entries are:
REM
bias comes from the remote bias source
LOC
bias is from the local source (entered by operator at console)
OFF
controller does not use a bias signal
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......