Appendix A Runtime Templates
Device Loop Templet
3BUR002418-600 A
229
Valid entries are:
YES
enable
NO
disable
REVERT COMMAND Field
This field specifies the command to which DEV_CMND is automatically set as part
of revert.
Valid entry is:
a command from the descriptor set defined for the device on its Device
Descriptor Templet
CUTOUT ENABLE Field
This field specifies whether cutout is enabled for the loop. Cutout allows an FCM of
this or another loop to control the posting of the alarms.
Valid entry is:
YES
enable the cutout feature
NO
disable the cutout feature
OUTPUT ERROR ACTION Field
This field specifies the actions taken when the output driver fails.
Valid entries are:
NOTHING
continue normal processing
GOTO BACKUP
processing goes to the Backup Controller Module if one is
present. This option shuts down CCF processing in a
Multibus subsystem when the driver fails.
LOOP OFF
turn the loop off
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......