BAD OUTPUT ALARMS Field
This field specifies whether the bad data quality alarm for the output signal is
enabled. If this field is YES, an alarm occurs when the data quality of the output
goes to BAD. Valid entries are: YES (enable the alarm), NO (disable the alarm).
SETPOINT HIGH ALARMS Field
This field specifies whether the high alarm for the setpoint signal is enabled. If this
field is YES, an alarm occurs when the output is equal to or greater than the value
entered in the SETPOINT HIGH LIMIT field. Valid entries are: YES (enable the
alarm), NO (disable the alarm).
SETPOINT LOW ALARMS Field
This field specifies whether the low alarm for the setpoint signal is enabled. If this
field is YES, an alarm occurs when the setpoint is equal to or less than the value
entered in the SETPOINT LOW LIMIT field. Valid entries are: YES (enable the
alarm), NO (disable the alarm).
BAD SETPOINT ALARMS Field
This field specifies whether the bad data quality alarm for the setpoint signal is
enabled. If this field is YES, an alarm occurs when the data quality of the setpoint
goes to BAD. Valid entries are: YES (enable the alarm), NO (disable the alarm).
DEVIATION HI ALARMS Field
This field specifies whether the high alarm for the deviation signal is enabled. If this
field is YES, an alarm occurs when the deviation is equal to or greater than the value
entered in the DEVIATION HIGH LIMIT field. Valid entries are: YES (enable the
alarm), NO (disable the alarm).
DEVIATION LOW ALARMS Field
This field specifies whether the low alarm for the deviation signal is enabled. If this
field is YES, an alarm occurs when the deviation is equal to or greater than the value
entered on the DEVIATION LOW LIMIT field. Valid entries are: YES (enable the
alarm), NO (disable the alarm).
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......