Loop Definition Templet
Appendix A Runtime Templates
214
3BUR002418-600 A
PROCESSING RATE Field
Specifies the interval at which the loop is processed (scanned). This field, the
PROCESSING PHASE, and BASERATE fields interact to determine the actual
loop processing rate. Scan Rate (Loop Detail display) equals the Processing Rate
divided by the Base Rate. If the Base Rate is 0.5 and the Processing Rate is 1.0, then
the Scan Rate is 2.0.
Valid entry is in the form of an integer equivalent of hr:min:sec.
The minimum acceptable value is the base rate of the module (0.1 to 1.0) as
specified on the CCF Templet. The maximum value is 65535 times the base rate (if
the base rate is 0.25 then the maximum is 16383.75). The value entered on this field
is automatically rounded up to the next higher multiple of the base rate.
Loop Definition Template entry examples:
PROCESSING PHASE Field
Use this field to distribute processing for the loops about the processing interval.
This field, the PROCESSING RATE, and BASERATE fields interact to determine
the loop processing rate. Valid entry is: any integer from 0 to PROCESSING RATE
/ BASERATE - 1 (rounded up to the next higher integer if not a whole number). If
an entry is greater than the valid maximum, the phase is set to 0.
TREND RATE Field
Specifies the rate at which the trend data for the measured variable is collected.
Valid entries are the following number of seconds:
0 (no trend collection), 6, 12, 60, 120, 360, 720, 1440, 2880
Runtime Entry
Configurator Entry
Interpreted as:
0.25
.25
.25 seconds
5
5
5 seconds
257
4:17 or 257
4 minutes 17 seconds
7744
2:09:04 or 7744
2 hours 9 minutes 4 seconds
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......