Section 3 CCF Displays
Engineer Tuning Displays for a Device Loop
3BUR002418-600 A
57
Tuning changes are made to database attributes by first changing the information on
the templet and then saving the templet information to the database by selecting the
SAVE
button. If the save process is not successful, a message describing the
problem is displayed. After corrective action is taken, you can re-attempt the save
process. Use the
X
button to exit the templet.
Runtime Version of Breakpoint Sets Templet
The runtime version of the Breakpoint Sets Templet (Linearization Update Display)
is used to change the values of a specific breakpoint set without having to recompile
and install the entire CCF configuration of the node. The templet is accessed via the
Loop FCM Display LINEAR TBL button when a TABLE FCM is selected.
Set the X VALUE, Y VALUE pairs in the edit window using floating point numbers.
Enter from 2 up to 11 x,y pairs. When all required changes to the values are made,
send the new values to the database by selecting the SAVE button. If the save
process is not successful, a message describing the problem is displayed.
SAVE changes both the active database in the subsystem containing the loop and
the installed database on the disk in the node where the configuration software
resides. However, the Breakpoint Sets Templets originally used to configure the
database is not immediately modified. It retains the old values until the database is
decompiled. Instructions for decompiling a database are provided in
AdvaBuild
Basic Functions User’s Guide
for the Advant Station-based AdvaBuild software.
There is no log of the changes made to the breakpoint sets.
Engineer Tuning Displays for a Device Loop
Access the runtime version of the Device Loop Templet by:
Tuning changes affect both the active database in the subsystem containing the
loop and the installed database on the disk in the node where the AdvaBuild
configuration software resides. Matching the installed database with the
operational database allows tuning changes to remain in effect when a subsystem
or control module is rebooted.
Templets originally used to configure the database retain the old value until the
database is decompiled. Instructions for decompiling a database are provided in
AdvaBuild Basic Functions User’s Guide
for the Advant Station-based
AdvaBuild software.
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......