DO810
Appendix A Runtime Templates
310
3BUR002418-600 A
DQ CYCLE TIME
Enter the channel data quality update period (msec) over the fieldbus. Refer to the
S800 I/O User’s Guide
for details of AF 100 loading in relation to cycle time.
The valid values are:
1, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024, 2048, and 4096
The default value is 128.
LABEL
Enter a characteristic name to identify the DO810 or DO890 Module of the station.
The name may contain up to 20 characters.
MONITOR POWER
To monitor process power source enter a
YES
; if not needed enter a
NO
.
DO890 with any channel supervision requires that MONITOR POWER =
YES
.
Default Value is NO.
OSP HOLD 01 through 16
If an OSP TIMEOUT has occurred, will the DO810 hold the last value during OSP?
Enter a
YES
if it will, or enter a
NO
if an OSP VALUE will be used.
The Default is NO.
OSP TIMEOUT
Enter the time (msec) after communications is lost, that outputs go to OSP value.
The valid values are:
OFF, 256, 512, and 1024.
The default value is 1024.
For the DO890 module, enter a description that includes the module type for
future reference to help alleviate confusion with an DO890 being used in the
DO810 templet.
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......