TRIO LAN Display
Section 7 I/O Displays
182
3BUR002418-600 A
TRIO LAN Status Area
The TRIO LAN status area represents the Field Bus Interface as described below.
Redundancy
Possible values are:
AVAILABLE - Redundancy is configured and enabled. When
it is available, the system switches buses when
communications with an active block is lost. You are not
allowed to switch single blocks between the buses.
NOT AVAILABLE - Redundancy is configured, but not
enabled (for the AC 460, one of the CI560 TRIO MIB
submodules is either MISSING, FAILED, or READY).
NOT CONFIGURED - Redundancy is not configured on the
REMOTEIO templet.
Diag.
Checking
Enabled or Disabled. Use this field to enable or disable diagnostic
checking for all blocks on the Field Bus.
Bus A or
Bus B
Use the context menu associated with the Bus A or Bus B status
and select the appropriate command to do the following:
Select
Diagnostics
and from the submenu
select:
•
Enable
,
•
Disable
or
•
Clear All
(to clear all diagnostics for every
block on the bus)
Select
Activate All
to activate all inactive blocks on the bus (either
bus for the AC 460). This is equivalent to all blocks signing into
CCF. When a block is not active, CCF channels related to it are
given a BAD data quality. This does not change any configuration
parameters of the block. If a block was made inactive via its TRIO
Block Display, this command can be used to activate it.
Select
Redundancy
and from the submenu select:
•
Establish
,
Terminate
, or
Switch Bus
(see
•
Activate Bus
,
Deactivate Bus
,
Restart Bus
or
Switch Bus
(see
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......