Section 7 I/O Displays
TRIO LAN Display
3BUR002418-600 A
183
Redundancy on the SC Controller
You will be asked to Confirm or Cancel redundancy requests.
Use
Establish
on a bus with redundancy configured and NOT AVAILABLE to
make it AVAILABLE.
Use
Terminate
on a bus that is AVAILABLE to make it NOT AVAILABLE.
Use
Switch Bus
to force a switchover to the other bus.
Redundancy on the AC Controller
You will be asked to Confirm or Cancel redundancy requests.
Use
Deactivate Bus
on a bus with redundancy AVAILABLE, bus state ACTIVE
and no blocks using it to change the bus state to READY and redundancy to NOT
AVAILABLE.
Use
Activate Bus
on a bus with redundancy NOT AVAILABLE and bus state
READY to change the bus state to ACTIVE and redundancy to AVAILABLE.
Mod/Sub
This field represents the slot number of the of the controller carrier
Module, and the Submodule location of the CI560 TRIO MIB
submodule (AC). This field is N/A on the SC controller.
State
This field shows the status of the CI560 submodule (AC).
ACTIVE indicates the submodule is in use.
FAILED means the submodule has stopped or no redundant
bus is configured.
MISSING means there is not a submodule installed in this
location.
READY means the redundant bus is deactivated.
This field is N/A on the SC controller
MSEC
This field gives the scan time in milliseconds for the Field Bus as
computed by the Advant OCS.
HHM
IN USE, NOT IN USE. This field indicates if a Hand-held Monitor
(HHM) is being used on the bus.
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......