PID Controller FCM
Appendix A Runtime Templates
242
3BUR002418-600 A
OUTPUT LOW LIMIT Field
This field specifies the low limit for the output signal. It is used to limit the output
when the FCM is in the modes specified in the LIMITED OUTPUT MODES field.
It is also the alarm limit if the entry in the OUTPUT LOW ALARMS? field is YES.
Valid entry is a number between -14.0 and 114.0%.
OUTPUT ALARM DB Field
This field is used to define a deadband for the output alarm of this FCM. Valid entry
is a floating point number in percent of range.
OUTPUT RATE LIMIT Field
This field specifies the highest allowed rate of change of the output signal per
second. It is used when the FCM is in the modes specified in the LIMITED
OUTPUT MODES field (except for MAN, OUTPUT RATE LIMIT is not
applicable for manual mode). It is also the alarm limit if the entry in the OUTPUT
RATE ALARMS? field is YES. Valid entry is a number between 0.0 and 128.0%.
SETPOINT HIGH LIMIT Field
This field specifies the high limit for the setpoint values. This limit only applies to
the setpoint modes specified in the LIMITED SETPT MODES field. It is also used
as an alarm limit when the entry in the SETPOINT HIGH ALARMS? field is YES.
Valid entry is a decimal value in engineering units.
SETPOINT LOW LIMIT Field
This field specifies the low limit for the setpoint values. This limit only applies to
the setpoint modes specified in the LIMITED SETPT MODES field. It is also used
as an alarm limit when the entry in the SETPOINT LOW ALARMS? field is YES.
Valid entry is a decimal value in engineering units.
DEVIATION HIGH LIMIT Field
This field specifies the high alarm limit for the deviation value (normalized
measured value input to the PID FCM is greater than the PID setpoint by this
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......