Appendix A Runtime Templates
AO820
3BUR002418-600 A
299
The default value is 128.
LABEL
Enter a characteristic name to identify the AO820 Module of the station. The name
may contain up to 20 characters.
OSP HOLD 01 through 04
If an OSP TIMEOUT has occurred, will the AO810 hold the last value during OSP?
Enter a
YES
if it will, or enter a
NO
if an OSP VALUE will be used.
The Default is NO.
OSP TIMEOUT
Enter the time (msec) after communications is lost, that outputs go to OSP value.
The valid values are:
OFF, 256, 512, and 1024.
The default value is 1024.
OSP VALUE 01 through 04
Enter the channel value in counts to output after an OSP TIMEOUT. If the OSP
HOLD has been selected as the OSP value then this field entry is ignored.
The default is 0.
The valid values are:
0 to 28480.
Where 0 = 0 mA and 28480 = 20 mA.
Output
Range
Minimum
Count
Maximum
Count
Counts
-10 - 10V
-28480
28480
2848 V/count
-20 - 20MA
-28480
28480
1424 mA/count
Summary of Contents for Ability 800xA Series
Page 1: ...Power and productivity for a better worldTM 800xA for MOD 300 Operation System Version 6 0 ...
Page 2: ......
Page 3: ...800xA for MOD 300 Operation System Version 6 0 ...
Page 14: ...Table of Contents 14 3BUR002418 600 A ...
Page 74: ...Area Graphic Display Section 3 CCF Displays 74 3BUR002418 600 A ...
Page 102: ...Batch Connectivity to M0D 300 Section 4 TCL Displays 102 3BUR002418 600 A ...
Page 120: ...TLL Messages Section 5 TLL Displays 120 3BUR002418 600 A ...
Page 212: ...Viewing Abnormal State on MOD Loop Displays Section 8 Operation Examples 212 3BUR002418 600 A ...
Page 320: ...BRKPTS Appendix A Runtime Templates 320 3BUR002418 600 A ...
Page 322: ...Updates in Revision Index A 322 3BUR002418 600 A ...
Page 330: ...Index 330 3BUR002418 600 A ...
Page 331: ......