6.5 Connecting Regenerative Resistors
6-37
6
(c) SERVOPACK’s with Capacities of 6.0 kW or More
No built-in regenerative resistor is provided, so the external regenerative resistor is required. The special
regenerative resistor units are as follow:
The following diagram shows the connection method between the SERVOPACK and the regenerative resis-
tor unit.
Note: Connect a regenerative resistor unit between B1 and B2 terminals. The regenerative resis-
tor unit is provided by the customer.
Main Circuit
Power Supply
Applicable
SERVOPACK
Model SGDH-
Applicable
Regenerative
Resistor Unit
Resis-
tance
(
Ω
)
Specifications
Three-phase
200 V
60AE
JUSP-RA04
6.25
25
Ω
(
220 W
)
×
4 (parallel connection)
75AE to -1EAE
JUSP-RA05
3.13
25
Ω
(
220 W
)
×
8 (parallel connection)
Three-phase
400 V
60DE, -75DE
JUSP-RA18
18
18
Ω
(
220 W
)
×
4 (direct/parallel connection)
1ADE, -1EDE
JUSP-RA19
14.25
28.5
Ω
(
220 W
)
×
8 (direct/parallel connection)
L1
L2
L3
U
B2
B1
+
V
W
W
ARNING
MODE/SET
DATA/
Ver.
POWER
BATTERY
CHARGE
SGDH-
SERVOPARK 200V
YASKAWA
Regenerative Resistor Unit
JUSP-RA
SERVOPACK