Baseload PID Screen
The purpose of this screen is to configure the Baseload PID. This screen has a live trend where it is
possible to check the PV (Load) in red, Setpoint in green and the PID output in blue.
It is also possible to tune the PID.
Figure 4-26. Baseload PID Screen
Table 4-19. Baseload PID Configuration Settings
P
0.48 (0.0, 100.0)
Visibility: Always
The Proportional Gain Input determines the gain of the
proportional component of the block's response.
User Level: Service
I
0.2 (0.0, 10.0)
Visibility: Always
The Integral Gain Input determines the gain of the integral
component of the block's response.
User Level: Service
D
100.0 (0.01, 100.0)
Visibility: Always
The Speed Derivative Ratio (S_D_R) input affects the derivative
component of the block's response.
User Level: Service
The operator can navigate between the other PID´s screens pressing the soft key with right arrow.
To change the settings of the trend press the soft key “Settings” and the below screen will pop up.
Figure 4-27. Baseload PID Settings Screen