Manual 35116
505HT for Pelton Turbines
Woodward
11
Chapter 1.
General Information
Information
This manual describes the Woodward 505HT Digital Governor for Pelton Turbines, including:
•
Up to 6 nozzles
•
Digital Deflector
The option charts below shows the part numbers and the differences between the models. This manual
does not contain instructions for the operation of the complete turbine system. For turbine or plant
operating instructions, contact the plant-equipment manufacturer.
Part Number options
Part Number Description
8200-1400
505H (LV-STD) PELTON TURBINE CONTROL
8200-1401
505H (HV-STD) PELTON TURBINE CONTROL
Terminology
505
Refers to the overall Woodward Product family / hardware platform
505XT
Refers specifically to the Control/GUI application software features described in this manual –
identified on unit p/n label and logo on Home screen
General Installation and Operating Notes and Warnings
Peripheral equipment must be suitable for the location in which it is used.
Note: For additional installation and operating information, see the
Regulatory Compliance section of this manual.
Controller Overview
The 505HT is field programmable which allows a single design to be used in many different control
applications and reduces both cost and delivery time. It uses a built in graphical user interface (GUI) with
multi-lingual menu driven screens to instruct site engineers on configuring the control to a specific
application. The 505HT can be configured to operate as a stand-alone unit or in conjunction with a plant’s
Distributed Control System.
Designed for hydro turbine control, the 505HT control includes three PID controllers (Offline, Online e
Baseload), start-up routine, and multiple protection functions overspeed, Small System Detection, etc.)
which can be configured by a user depending on the specific turbine application’s requirements. Users
can configure the 505’s different PID controllers, start routines, discrete and analog I/O functions and
protection levels themselves without the need for a special control engineer. A first-out indication feature
for system shutdowns reduces troubleshooting time. Once configured, the 505HT performs a
configuration check routine to ensure that the programmer did not make any basic configuration mistakes.
This control is exclusive for Pelton Turbines up to 6 (six) nozzles. The Actuator output 1 is dedicated to
nozzle 1 and the actuator output 2 is dedicated to nozzle 2. If the turbine has more than 2 nozzles it is
necessary to use analog outputs to the other(s) nozzle(s). Front panel ESTOP button will shut down the
actuators circuits 1 and 2, so if this is not desired to the control, configure analog outputs to this function.
Released
Содержание 505HT
Страница 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Страница 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Страница 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Страница 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...