Manual 35116
505HT for Pelton Turbines
Woodward
144
mA at 100% Demand
20.0 (0.0, 25.0) mA
Visibility: Always
Set the mA value that corresponds to 100% demand.
User Level: Service
Actuator Type
AO 01 Units
Visibility: Always
Choose if the actuator is Integral or proportional.
CONFIGURATION MODE REQUIRED
User Level: Configure
Actuator Direction
Direct
Visibility: Always
Choose if the actuator has direct or reverse actuation.
CONFIGURATION MODE REQUIRED
User Level: Configure
Offline Gain
1.0 (0.0, 50.0)
Visibility: If configured to integral
Type the offline gain of the actuator
User Level: Service
Online Gain
1.0 (0.0, 50.0)
Visibility: If configured to integral
Type the online gain of the actuator
User Level: Service
Offset
0.0 (-100.0, 100.0)
Visibility: If configured to integral
Type the offset of the actuator
User Level: Service
If the control is in calibration mode it is possible to enter on the calibration screen pressing the soft key
“Force Output” to force this output.
Released