Manual 35116
505HT for Pelton Turbines
Woodward
20
Electromagnetic Compatibility (EMC)
The Flex500 product family complies with Heavy Industrial EMC requirements per EN 61000-6-4 & EN
61000-6-2 specifications. Marine Type Approval is also met per IACS UR E10 EMC test requirements
when a Marine qualified version is used.
Emissions EN 61000-6-4 & IACS UR E10
•
Radiated RF Emissions Limits 150 kHz to 5000 MHz per IEC 61000-6-4 & Marine Type Approval.
•
Power Line Conducted RF Emissions Limits 10 kHz to 30 MHz per IEC 61000-6-4 & Marine Type
Approval.
Immunity EN 61000-6-2 & IACS UR E10
•
Electrostatic Discharge (ESD) immunity to ±6 kV contact / ±8 kV air per IEC 61000-4-2.
•
Radiated RF Immunity to 10 V/m from 80 MHz to 3000 MHz per IEC 61000-4-3.
•
Electrical Fast Transients (EFT) Immunity to ±2.0 kV on I/O and Power Supply inputs per IEC 61000-
4-4.
•
Surge Immunity on DC Power Supply inputs to ±1.0 kV line to earth and ±0.5 kV line to line per IEC
61000-4-5.
•
Surge Immunity on AC Power Supply inputs to ±2.0 kV line to earth and ±1.0 kV line to line per IEC
61000-4-5.
•
Surge Immunity on I/O to ±1.0 kV line to earth per IEC 61000-4-5.
•
Conducted RF Immunity to 10 V (rms) from 150 kHz to 80 MHz per IEC 61000-4-6.
•
Conducted Low Frequency Injection Immunity at 10% of the nominal supply level from 50 Hz to 12
kHz on Power Inputs per Marine Type Approval test requirements.
Outline Drawing for Installation
The physical outline dimensions for the 505 control are shown below. See Woodward Reference drawing
9989-3210 for additional details if necessary.
This 505 unit has the identical mounting hole pattern as the previous
version, however the holes do not come through the front of this unit;
therefore mounting screws of correct length must be used.
Mounting of the 505HT and Flex500 with the LCD Display and Keypad
must be in the vertical orientation with the ventilation slots at the top
and bottom of the control. The surrounding air temperature of the
control cannot exceed 70°C.
Panel Mounting information –
•
There are 8 x 10-32 UNF-2B tapped holes that are used to mount the 505.
•
The holes are tapped to 0.312” min Depth. Choose the proper length screw to not exceed this depth
into the Bezel.
•
Use screw 1069-949 (.375 Long, 10-32) for panel thickness (including washers) .065” - .100"
•
Use screw 1069-948 (.438 Long, 10-32) for panel thickness (including washers) .101”- .125”
•
Use screw 1069-946 (.500 Long, 10-32) for panel thickness (including washers) .126” - .187”
Released
Содержание 505HT
Страница 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Страница 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Страница 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Страница 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...