Manual 35116
505HT for Pelton Turbines
Woodward
90
Table 4-15. General Configuration (8/9) Screen Command Buttons and Parameters
Open Breaker on Normal Stop
Command
FALSE
Visibility: Always
Select if a command to open the generator breaker will be
issued when a Normal stop is in progress and the gate limit is at
speed no load value for “Minimum Nozzle Limit Timeout”.
User Level: Service
Minimum Nozzle Limit Timeout
2.0 (1.0, 30.0) s
Visibility: Always
Time the 505 will wait at speed no load reference to send a
command to open the generator breaker during a normal stop (if
enabled).
User Level: Service
Open Breaker on Unload
Command
FALSE
Visibility: Always
Select if a command to open the generator breaker will be
issued when an Unload is in progress and the load reference is
at Unload Level for “Minimum Load Reference Timeout”.
User Level: Service
Minimum Load Reference Timeout
10.0 (1.0, 300.0) s
Visibility: Always
Time the 505 will wait at unload reference to send a command to
open the generator breaker during an unload command (if
enabled).
User Level: Service
Screen Saver Delay
*4.0 (0.1, 24.0) h
Visibility: Always
Time the 505 will wait to start up the screen saver (in hours)
User Level: Service
Use Go to Status Screen
TRUE
Visibility: Always
If selected 505 will change the screen to the Status screen after
“Status Screen Delay” of inactivity. This is not screen saver.
User Level: Service
Status Screen Delay
30.0 (1.0, 600.0) min.
Visibility: Always
Time of inactivity that the 505 will wait to automatically jump to
Status screen (in minutes), if enabled.
User Level: Service
Jump to Alarm Screen when a new
Alarm Occurs
FALSE
Visibility: Always
If selected 505 will change the screen to the Alarm screen when
a new alarm occurs.
User Level: Service
The operator can navigate between the general configuration screens pressing the soft keys with arrows
to left or right.
Released
Содержание 505HT
Страница 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Страница 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Страница 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Страница 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...