Manual 35116
505HT for Pelton Turbines
Woodward
24
This module has been factory configured with fixed Ethernet IP
addresses of
•
Ethernet #1 (ETH1) = 172.16.100.15, Subnet Mask = 255.255.0.0
•
Ethernet #2 (ETH2) = 192.168.128.20, Subnet Mask =
255.255.255.0
•
Ethernet #3 (ETH3) = 192.168.129.20, Subnet Mask =
255.255.255.0
•
Ethernet #4 (ETH4) = 192.168.130.20, Subnet Mask =
255.255.255.0
Each of the ETHERNET ports is required to be configured for a unique
subnet (domain) (view default settings as an example).
Table 2-3. Ethernet Ports #1-4 (10/100)
Board Connection
Description
Pin 1 – TX+
Pin 2 – TX-
Pin3 – RX+
Pin 4 – Not used
Pin 5 – Not used
Pin 6 – RX-
Pin 7 – Not used
Pin 8 – Not used
SHIELD = Chassis GND
Network Configuration Utility (AppManager)
Woodward's AppManager™ software can be used to configure network setting and load Control software
(GAP), HMI display software (QT), and operating system service packs. The AppManager utility can be
downloaded from
www.woodward.com/software
.
A PC connection must be made to Ethernet #1 (ETH1) using a RJ45 Ethernet cable.
Note: AppManager can always be used to “discover/view” the current CPU IP Address. However, to
modify settings or load applications, the PC running AppManager must be reconfigured to be on the
same “network” as the CPU.
•
Locate the ControlName on the module faceplate and highlight it in AppManager.
•
To VIEW the IP address configuration, select menu option CONTROL - CONTROL
INFORMATION. Look for the Ethernet adapter addresses under the Footprint Description.
•
To CHANGE the IP address configuration, select menu option CONTROL - CHANGE NETWORK
SETTINGS.
Communications (CAN)
Four (4) Isolated CAN ports are available for general communications as well as simplex or redundant
distributed control. Compatible devices include Woodward RTCnet nodes, LINKnet HT nodes, DVP valve
products, and other 3rd party devices. Removable latching connector plugs are provided for field wiring.
Network Termination: CAN networks must include a 120
Ω
termination resistor at each end of the trunk
line.
Released
Содержание 505HT
Страница 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Страница 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Страница 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Страница 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...