Manual 35116
505HT for Pelton Turbines
Woodward
104
Nozzle Rotation Screen
The purpose of this screen is to configure the automatic nozzle rotation and to provide a way to manually
rotate the nozzles. This screen will be available if the turbine has more than one nozzle.
Figure 4-34. Nozzles Rotation Screen
Table 4-25. Nozzle Rotation Screen Configuration Values
Enable Rotation by Timer
TRUE
Visibility: Always
Enable rotation by timer. If enabled the 505 will rotate the
nozzles at each programmed time. The time counts only when
the turbine is running.
User Level: Service
Timer Between Rotation
150.0 (0.1, 600.0) h
Visibility: Always
Time (in hours) to automatic rotate nozzles, if rotate by time is
enabled.
User Level: Service
Remaining Time
Monitor
Visibility: Always
Remaining time (in hours) to the next rotation, if rotate by time is
enabled.
User Level: Monitor
Enable Rotation by Nozzle Fail
FALSE
Visibility: Always
Enable rotation if a nozzle in use has a position status signal
failed or a gross mismatch (large difference between demand
and actual position).
User Level: Service
Force Rotation
Command
Visibility: Always
Command to force the rotation of the nozzles. If any of the non-
selected nozzles has either a signal failure or a gross mismatch
the rotation command is inhibited
User Level: Service
There are some nozzle statuses at the right of the screen.
Released
Содержание 505HT
Страница 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Страница 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Страница 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Страница 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...