Manual 35116
505HT for Pelton Turbines
Woodward
167
Event ID
Description
Explanation
53
Nozzle #4 Feedback not
necessary
Control is configured to not use nozzle 4 but there’s
an AI configured for “Nozzle #4 Position Feedback”
54
Nozzle #5 Feedback not
necessary
Control is configured to not use nozzle 5 but there’s
an AI configured for “Nozzle #5 Position Feedback”
55
Nozzle #6 Feedback not
necessary
Control is configured to not use nozzle 6 but there’s
an AI configured for “Nozzle #6 Position Feedback”
56
Pond or Tail Level (AI) not
configured
There’s a DI configured for “Pond/Tail Level Control
Enable”, but no AI configured for “Pond/Tail Level”
57
Speed Bias DI (R/L) not
configured
Speed Bias is configured for digital option, but either
“Speed Bias Raise” or “Speed Bias Lower” DI is not
configured
58
Speed Bias AI is not Necessary
Speed Bias is not configured for analog option, but
there’s an AI configured for “Speed Bias”
59
Speed Bias AI not configured
Speed Bias is configured for analog option, but there’s
no AI configured for “Speed Bias”
60
Speed Bias DI is not Necessary
Speed Bias is not configured for digital option, but
there’s a DI configured for either “Speed Bias Raise”
or “Speed Bias Lower”
61
Remote Speed AI Not Configured
“Use Remote Speed Control” is checked, but there’s
no AI configured for “Remote Speed Reference”
62
Remote Baseload AI Not
Configured
“Use Remote Baseload Control” is checked, but
there’s no AI configured for “Remote Baseload
Reference”
63
Remote Level AI Not Configured
“Use Remote Level Control” is checked, but there’s no
AI configured for “Remote Level Reference”
64
Remote Speed AI Not Necessary
“Use Remote Speed Control” is unchecked, but
there’s an AI configured for “Remote Speed
Reference”
65
Remote Baseload AI Not
Necessary
“Use Remote Baseload Control” is unchecked, but
there’s an AI configured for “Remote Baseload
Reference”
66
Remote Level AI Not Necessary
“Use Remote Level Control” is unchecked, but there’s
an AI configured for “Remote Level Reference”
67
Remote Speed DI Not Necessary
“Use Remote Speed Control” is unchecked, but
there’s a DI configured for “Enable Remote Speed”
68
Remote Baseload DI Not
Necessary
“Use Remote Baseload Control” is unchecked, but
there’s a DI configured for “Enable Remote Baseload”
69
Remote Level DI Not Necessary
“Use Remote Level Control” is unchecked, but there’s
a DI configured for “Enable Remote Level”
70
Gen Power AI Not Configured
“Use Baseload Control” is checked, but there’s no AI
configured for “Remote Baseload Reference”
Released
Содержание 505HT
Страница 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Страница 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Страница 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Страница 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...