Communications (Ethernet) Screen
The purpose of this screen is to configure Ethernet communication ports. There are two available
Ethernet links and they can be programmed on this screen. The screen has the same configuration for
both ports, but the explanation will be made for just the port 1, as the port 2 has the same parameters.
Figure 4-46. Communications (Ethernet) Screen
Table 4-37. Communications (Ethernet) Screen Configuration Values
Use Ethernet 1
FALSE
Visibility: Always
Select if the Ethernet specific port communication will be used.
User Level: Service
Timeout
10.0 (0.5, 30.0) s
Visibility: Always
Enter the timeout for the Ethernet port.
User Level: Service
ASC-II / RTU
RTU
Visibility: Always
Enter the ASC-II or RTU for the Ethernet port.
User Level: Service
Network Address
2 (1, 247)
Visibility: Always
Enter the ASC-II or RTU for the Ethernet port.
User Level: Service
Enable Analog Write
FALSE
Visibility: Always
Enable the analog write for the Ethernet port. If disable won’t be
possible to write any analog value through this port.
User Level: Service