Manual 35116
505HT for Pelton Turbines
Woodward
125
Enable Boolean Write
FALSE
Visibility: Always
Enable the Boolean write for the Ethernet port. If disable won’t be
possible to write any Boolean value through this port.
User Level: Service
Link Error is Shutdown
FALSE
Visibility: Always
Enable if a link error on this port should shutdown the turbine.
CONFIGURATION MODE REQUIRED
User Level: Configure
Enable Shutdown via Modbus
TRUE
Visibility: Always
The first Boolean write address is designated to shutdown the
turbine. Select if this shutdown command can be used.
CONFIGURATION MODE REQUIRED
User Level: Configure
This parameter is common to both serial and Ethernet ports. If
enabled or disabled on the serial port will disable on the Ethernet
port also.
To set the IP address of the port the operator should press the soft key “Set IP”.
Communications (Ethernet IP) Screen
The purpose of this screen is to configure IP for the Ethernet ports communication.
Figure 4-47. Communications (Ethernet IP) Screen
Each of the ETHERNET ports is required to be configured for a unique
subnet (domain) (view default settings as an example).
The IP’s can be set by other service tools.
The top of the screen shows the current IP addresses in use on for
each port.
Released
Содержание 505HT
Страница 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Страница 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Страница 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Страница 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...