Manual 35116
505HT for Pelton Turbines
Woodward
14
17 - Remote Fault #2
18 - Remote Fault #3
19 - Remote Fault #4
20 - Remote Fault #5
21 - Remote Fault #6
22- Manual Nozzle #1 Enable
23- Manual Nozzle #2 Enable
24- Manual Nozzle #3 Enable
41- Deflector Manual Close
42- Deflector Closed
43- Deflector Opened
44- Enable Remote Speed
45- Enable Remote Baseload
46- Enable Remote Level
47- Overspeed test Enable
48 – Force Nozzle Rotation
Control Outputs
Actuator Outputs
Two 4-20mA or 20-160mA actuator outputs are available for use. These outputs are defined to be used
as Nozzle 1 and nozzle 2 and cannot be used for other functions.
Front panel ESTOP button will shutdown the actuators circuits 1 and
2, so if this is not desired to the control, configure analog outputs to
this function. Some valves should remain with 4mA during the
shutdown, and these actuator outputs will not work for this case.
Analog 4-20mA Outputs
Six 4–20 mA analog outputs are available for use and each can be configured as one of the following
output functions:
Table 1-3. Selectable functions for 4-20mA Analog Outputs
1- Not Used
2- Tachometer
3- Nozzle 1 Position
4- Nozzle 2 Position
5- Nozzle 3 Position
6- Nozzle 4 Position
7- Nozzle 5 Position
8- Nozzle 6 Position
9- Nozzle Limit
10- Speed Adjustment
11- Pond/Tail Level
12- Pond/Tail Level Setpoint
13- Speed Bias
14- Generator Power
15- Nozzle 1 Actuator
16- Nozzle 2 Actuator
17- Nozzle 3 Actuator
18- Nozzle 4 Actuator
19- Nozzle 5 Actuator
20- Nozzle 6 Actuator
Relay Outputs
Eight Form-C relay contact outputs are available. The first channel is dedicated to be a Close Deflector
output. The other seven are configurable relays. Each relay can be programmed to provide a contact
related to a conditional state as listed.
Table 1-4. Selectable functions for Relay Outputs
1- Not Used
2- Nozzle Position Switch #1
3- Nozzle Position Switch #2
4- Nozzle Position Switch #3
5- Nozzle Position Switch #4
6- Speed Switch #1
7- Speed Switch #2
8- Speed Switch #3
9- Speed Switch #4
10- Speed Switch #5
11- Speed Switch #6
12- General Shutdown
13- General Governor Alarm
14- Creep indication
22- Active Power Switch #4
23- Ready for Start
24- Turbine Stable Speed
25- Reset Command
26- Close Deflector
27- Open Deflector
28- All Nozzle Position Signal Fail
29- Level Signal Fail
30- Remote Speed Signal Fail
31- Speed Bias Input Signal Fail
32- Incomplete Start
33- All Nozzle position Major Mismatch
34- Total Speed Signal Fail
35- Speed Signal #1 Fault
Released
Содержание 505HT
Страница 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Страница 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Страница 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Страница 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...