Manual 35116
505HT for Pelton Turbines
Woodward
36
Hardware - Discrete Inputs
This control provides an isolated group of (20) discrete input channels for use with +24 V (dc) signals. An
isolated Contact Power voltage supply of +24 V (dc) is provided to use with the discrete inputs. This
supply includes short-circuit and over-voltage protection.
Note: Do not use the Contact Power output to power any other devices.
Features
•
(20) Discrete Input Channels for +24 V (dc) signals
•
+24 V Contact Power with short-circuit and diode protection
•
Isolated power and discrete input group
•
Woodward GAP block, diagnostics, and configuration support
•
GAP configurable update rates of 5 ms to 160 ms
•
Time-stamping capability (1 ms)
Table 2-14. Specifications (DI)
Number of Channels: 20
DI Input Low State: (0 to 8) V (dc)
DI Input High State: (16 to 32) V (dc)
DI Input Current: < 5 mA per channel
DI Input Impedance: 25K approximate
DI Hardware Filter: 1.0 ms approximate at room temp
DI Channel Isolation: 0 V channel to channel
500 Vrms to EARTH and all other I/O
DI Overvoltage: Overvoltage to 36 V (dc) for inputs
Contact Power Output 24 V ±14 %, 150 mA (max), short circuit & diode protected
Contact Power Isolation 500 Vrms to EARTH and all other I/O
Figure 2-11. Discrete Input Block Diagram
Released
Содержание 505HT
Страница 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Страница 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Страница 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Страница 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...