Manual 35116
505HT for Pelton Turbines
Woodward
165
Event ID
Description
Explanation
17
AI#02 – Duplicated Function
This analog input has the same function of other AI
18
AI#03 – Duplicated Function
This analog input has the same function of other AI
19
AI#04 – Duplicated Function
This analog input has the same function of other AI
20
AI#05 – Duplicated Function
This analog input has the same function of other AI
21
AI#06 – Duplicated Function
This analog input has the same function of other AI
22
AI#07 – Duplicated Function
This analog input has the same function of other AI
23
AI#08 – Duplicated Function
This analog input has the same function of other AI
24
Deflector Closed DI not
programmed
“Use Deflector” option is selected but there’s no DI
configured for “Deflector Closed”
25
Deflector Opened DI not
programmed
“Use 2 Sensors” option is selected but there’s no DI
configured for “Deflector Opened”
26
Deflector Closed DI not Needed
“Use Deflector” option is not selected but there’s a DI
configured for “Deflector Closed”
27
Deflector Opened DI not Needed
“Use 2 Sensors” option is not selected but there’s a DI
configured for “Deflector Opened”
28
Nozzle #3 ACT output not
configured
Control is configured for at least 3 nozzles but no AO
is configured for “Nozzle 3 Actuator”
29
Nozzle #4 ACT output not
configured
Control is configured for at least 4 nozzles but no AO
is configured for “Nozzle 4 Actuator”
30
Nozzle #5 ACT output not
configured
Control is configured for at least 5 nozzles but no AO
is configured for “Nozzle 5 Actuator”
31
Nozzle #6 ACT output not
configured
Control is configured for 6 nozzles but no AO is
configured for “Nozzle 6 Actuator”
32
Nozzle #1 ACT output not
necessary
Control is configured to not use nozzle 1 but there’s
an AO configured for “Nozzle 1 Actuator”
33
Nozzle #2 ACT output not
necessary
Control is configured to not use nozzle 2 but there’s
an AO configured for “Nozzle 2 Actuator”
34
Nozzle #3 ACT output not
necessary
Control is configured to not use nozzle 3 but there’s
an AO configured for “Nozzle 3 Actuator”
Released
Содержание 505HT
Страница 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Страница 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Страница 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Страница 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...