Manual 35116
505HT for Pelton Turbines
Woodward
138
Click on buttons at left of the screen to go to the specific contact input and configure it, if necessary or
click on the “Contacts 9-16” or “Contacts 17-20” to see the others contact inputs. Below you can see the
explanation of the contact input configuration screen.
Figure 4-59. Contact Inputs Screen
There is the status of the input at the top of the page.
The contact input #1 to #5 have fixed functions and the parameter “Function” has no effect to these
contact inputs. The default values showed below are for the contact input #6.All other contact inputs have
the same parameters.
Table 4-45. Contact Inputs Screen Configuration Values
Function
DEFLECTOR CLOSED
Visibility: Always
Choose the function of the specific contact input.
CONFIGURATION MODE REQUIRED
User Level: Configure
Device tag
BI 06
Visibility: Always
This is a user entered field. It allows entry of a short description
or tag name for this channel.
User Level: Service
Invert Logic
FALSE
Visibility: Always
Check this box if the discrete input is inverted (normally closed).
User Level: Configure
The operator can navigate between the contact inputs pressing the soft keys with arrows to left or right.
Released
Содержание 505HT
Страница 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Страница 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Страница 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Страница 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...