Manual 35116
505HT for Pelton Turbines
Woodward
169
Event ID
Description
Explanation
89
Speed Bias Dig. Out. Not
Available
Speed Bias is not being used, but there’s a DO
configured for either for “Speed Bias Enabled” or
“Speed Bias Input Signal Fail”
90
Act. Pwr. Sw. Dig. Out. Not
Available
There’s no AI configured for “Generator Power”, but
there’s a DO configured for “Active Power Switch”
91
Level Dig. Out. Not Available
“Use Level Control” is unchecked, but there’s a DO
configured for “Level Signal Fail”
92
Rem. Speed Dig. Out. Not
Available
“Use Remote Speed Control” is unchecked, but
there’s a DO configured for “Remote Speed Signal
Fail”
93
Spd In. 1 Dig. Out. Not Available
Speed Sensor #1 is not being used and there’s a DO
configured for “Speed Signal #1 Fault”
94
Spd In. 2 Dig. Out. Not Available
Speed Sensor #2 is not being used and there’s a DO
configured for “Speed Signal #2 Fault”
95
Nozzle Lim. Dig. Out. Not
Available
There’s no AI configured for “Nozzle Position Limiter”,
but there’s a DO configured for “Analog Nozzle Limiter
Signal Fail”
96
Rem. Baseload Dig. Out. Not
Available
“Use Remote Baseload Control” is unchecked, but
there’s a DO configured for “Remote Baseload Signal
Fail”
97
Gen Power Dig. Out. Not
Available
There’s no AI configured for “Generator Power”, but
there’s a DO configured for “Power Transducer Signal
Fail”
98
At Least one Spd has to be MPU
or Prox
At least one speed input must be configured for either
MPU or Proximity Probe
99
Man. Nlz1 Enable DI not
Necessary
Control is configured to not use nozzle 1 but there’s a
DI configured for “Manual Nozzle #1 Enable”
100
Man. Nlz1 Raise DI not
Necessary
Control is configured to not use nozzle 1 but there’s a
DI configured for “Nozzle #1 Manual Raise”
101
Man. Nlz1 Lower DI not
Necessary
Control is configured to not use nozzle 1 but there’s a
DI configured for “Nozzle #1 Manual Lower”
102
Man. Nlz2 Enable DI not
Necessary
Control is configured to not use nozzle 2 but there’s a
DI configured for “Manual Nozzle #2 Enable”
103
Man. Nlz2 Raise DI not
Necessary
Control is configured to not use nozzle 2 but there’s a
DI configured for “Nozzle #2 Manual Raise”
104
Man. Nlz2 Lower DI not
Necessary
Control is configured to not use nozzle 2 but there’s a
DI configured for “Nozzle #2 Manual Lower”
105
Man. Nlz3 Enable DI not
Necessary
Control is configured to not use nozzle 3 but there’s a
DI configured for “Manual Nozzle #3 Enable”
106
Man. Nlz3 Raise DI not
Necessary
Control is configured to not use nozzle 3 but there’s a
DI configured for “Nozzle #3 Manual Raise”
Released
Содержание 505HT
Страница 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Страница 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Страница 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Страница 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...