Manual 35116
505HT for Pelton Turbines
Woodward
166
Event ID
Description
Explanation
35
Nozzle #4 ACT output not
necessary
Control is configured to not use nozzle 4 but there’s
an AO configured for “Nozzle 4 Actuator”
36
Nozzle #5 ACT output not
necessary
Control is configured to not use nozzle 5 but there’s
an AO configured for “Nozzle 5 Actuator”
37
Nozzle #6 ACT output not
necessary
Control is configured to not use nozzle 6 but there’s
an AO configured for “Nozzle 6 Actuator”
38
Nozzle #1 ACT output duplicated
Control is configured for at least 1 nozzle, but there’s
more than one AO is configured for “Nozzle 1
Actuator”
39
Nozzle #2 ACT output duplicated
Control is configured for at least 2 nozzles, but there’s
more than one AO is configured for “Nozzle 2
Actuator”
40
Nozzle #3 ACT output duplicated
Control is configured for at least 3 nozzles, but there’s
more than one AO is configured for “Nozzle 3
Actuator”
41
Nozzle #4 ACT output duplicated
Control is configured for at least 4 nozzles, but there’s
more than one AO is configured for “Nozzle 4
Actuator”
42
Nozzle #5 ACT output duplicated
Control is configured for at least 5 nozzles, but there’s
more than one AO is configured for “Nozzle 5
Actuator”
43
Nozzle #6 ACT output duplicated
Control is configured for 6 nozzles, but there’s more
than one AO is configured for “Nozzle 6 Actuator”
44
Nozzle #1 Feedback not
configured
Control is configured for at least 1 nozzle and it’s
configured for integral control, but no “Nozzle #1
Position Feedback” AI has been configured
45
Nozzle #2 Feedback not
configured
Control is configured for at least 2 nozzles and it’s
configured for integral control, but no “Nozzle #2
Position Feedback” AI has been configured
46
Nozzle #3 Feedback not
configured
Control is configured for at least 3 nozzles and it’s
configured for integral control, but no “Nozzle #3
Position Feedback” AI has been configured
47
Nozzle #4 Feedback not
configured
Control is configured for at least 4 nozzles and it’s
configured for integral control, but no “Nozzle #4
Position Feedback” AI has been configured
48
Nozzle #5 Feedback not
configured
Control is configured for at least 5 nozzles and it’s
configured for integral control, but no “Nozzle #5
Position Feedback” AI has been configured
49
Nozzle #6 Feedback not
configured
Control is configured for 6 nozzles and it’s configured
for integral control, but no “Nozzle #6 Position
Feedback” AI has been configured
50
Nozzle #1 Feedback not
necessary
Control is configured to not use nozzle 1 but there’s
an AI configured for “Nozzle #1 Position Feedback”
51
Nozzle #2 Feedback not
necessary
Control is configured to not use nozzle 2 but there’s
an AI configured for “Nozzle #2 Position Feedback”
52
Nozzle #3 Feedback not
necessary
Control is configured to not use nozzle 3 but there’s
an AI configured for “Nozzle #3 Position Feedback”
Released
Содержание 505HT
Страница 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Страница 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Страница 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Страница 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...