Fail Safe State
OPEN
Visibility: Always
Choose the fail-safe condition in case of both speed signal fail.
User Level: Service
Time to disable Fail Safe
*20.0 (0.0, 300.0) min
Visibility: Always
Time to disable fail safe condition since both speed signals fail.
After this time the switch will go back to its normal state.
User Level: Service
The operator can navigate between the switches pressing the soft keys with arrows to left or right or go to
the other switches pressing the soft keys “Load switches” or “Nozzle Switches” (when available).
Nozzle Switch Screen
The purpose of this screen is to configure the Nozzle Switches. There are four nozzle switches available
on the 505.
Figure 4-50. Nozzle Switches Screen
Table 4-41. Nozzle Switches Screen Configuration Values
High Value
1.0 (0.0, 200.0) %
Visibility: Always
Enter the high value (in %) for the specific speed switch.
User Level: Service
High Delay
*0.0 (0.0, 600.0) s
Visibility: Always
Enter the high delay time for the specific speed switch.
User Level: Service
Low Value
0.5 (0.0, 200.0) %
Visibility: Always
Enter the low value (in %) for the specific speed switch.
User Level: Service
Low Delay
*0.0 (0.0, 600.0) s
Visibility: Always
Enter the low delay time for the specific speed switch.
User Level: Service
Released
Содержание 505HT
Страница 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Страница 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Страница 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Страница 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...