Communications (Service Ports)
RS-232 Service Port
An isolated RS-232 service port is located on the CPU board. Isolation is specified at 500 Vrms and baud
rate is fixed at 115.2K baud, 8 data bits, no parity, 1 stop-bit, and no flow control. This port is for VxWorks
operating system use only and cannot be configured for application software use.
For debug use, a Woodward PN 5417-1344, USB to serial debug cable is required to attach this port to a
PC. This port is to be used by trained Field Service personnel only!
Table 2-9. CPU Service Port (3 pin, 2 mm)
Dura-Click connector (male)
Pin 1 – RS232 Transmit
Pin 2 – RS-232 Receive
Pin 3 – Signam Ground
USB Service Port
Note: A USB service port is provided for future use, but is disabled.