Manual 35116
505HT for Pelton Turbines
Woodward
22
Input Power Specification
Specifications (LV)
LV Input Voltage range: 18-36 Vdc
Input Power (max): < 77 W, 4.3 A max
Output Voltage Holdup time: > 14 ms with 24 Vdc input voltage
Isolation to other circuits: > 500 Vrms to all other circuits
Isolation to EARTH: > 500 Vrms to EARTH
Input Overvoltage Protection: ±60 Vdc @ 25 °C
Reverse Polarity Protection: 60 Vdc @ 25 °C
Input Undervoltage shutdown: ~11 Vdc, non-latching
Note: Breaker or power-line fusing of 8 A min is recommended to protect the power wiring network
from possible wiring shorts.
Specifications (HV)
HV Input Voltage range: 88-264 Vac / 90-150 Vdc
HV Input Frequency range: 45-65 Hz
Input Power (AC max): < 73 W, 1.6 A max
Input Power (DC max): < 73 W, 0.8 A max
Output Voltage Holdup time: > 30 ms with 110 Vac input voltage
Output Voltage Holdup time: > 120 ms with 220 Vac input voltage
Isolation to other circuits: > 3000 Vrms to all other circuits
Isolation to EARTH: > 1500 Vrms to EARTH
Input Overvoltage Protection ±375 Vdc @ 25 °C
Reverse Polarity Protection: 375 Vdc
Input Undervoltage Shutdown: ~65 Vdc, non-latching
Note: Breaker or power-line fusing of 3.5 A min is recommended to protect the power wiring network
from possible wiring shorts.
Power Connector
Input Power is provided through a 3 position, latching terminal block with removable plug. Green
connectors are used for low voltage DC units. Orange connectors are used for high voltage AC/DC units.
Table 2-2. Input Power Connector Pinout
Plug Type: Side entry 7.62 mm, 12 A,
pluggable with latching screw down
PIN
1
2
3
Name
L+
L-
EARTH
Description
Input Power (+)
Input Power (-)
Earth / shield connection
Electric Shock
To reduce the risk of Electrical Shock the Protective Earth (PE) must
be connected to the PE
terminal on the enclosure. The
conductor providing the connection must have a properly sized ring
lug and wire gauge equal to or larger than 4mm² (12AWG).
Visual Indicators (LED’s) & CPU Configuration
Released
Содержание 505HT
Страница 23: ...Manual 35116 505HT for Pelton Turbines Woodward 21 Figure 2 2 505D Outline Drawing Released...
Страница 196: ...Manual 35116 505HT for Pelton Turbines Woodward 194 Figure F 10 Deflector Logic Released...
Страница 197: ...Manual 35116 505HT for Pelton Turbines Woodward 195 Revision History New Manual Released...
Страница 198: ...Manual 35116 505HT for Pelton Turbines Woodward 196 Declarations Released...