Description
The Woodward 2301D controls load sharing and speed of generators driven by
diesel or gaseous engines. (These power sources are referred to as “prime
movers” throughout this manual.) The 2301D is a microprocessor-based digital
control designed to include the functions of and be compatible with 2301A load
sharing controls. The increased flexibility of software allows the 2301D to include
control functions that required additional equipment in previous versions of
2301A control systems. The 2301D therefore is suitable for upgrading existing
control systems or increased functionality in new installations.
The 2301D has the following Woodward part numbers:
8273-138
2301D-EC Load Sharing and Speed Control, 24 Vdc input, with
Modbus® *, Ordinary Locations
8273-139
2301D-EC Load Sharing and Speed Control, 24 Vdc input, with
Modbus, Hazardous Locations
8273-140
2301D Load Sharing and Speed Control, 24 Vdc input, Ordinary
Locations
8273-141
2301D Load Sharing and Speed Control, 24 Vdc input, Hazardous
Locations
*—Modbus is a registered trademark of Schneider Automation Inc.
The control is housed in a sheet-metal chassis and consists of a single printed
circuit board. The 2301D is set up and configured through an external computer
connected at the 9-pin connector at the front of the control. The configuration
software is supplied with each control.
The 2301D provides control in either isochronous, droop, or base load. The
2301D will allow for soft load transfer when being added to or removed from a
bus.
The isochronous mode is used for constant prime mover speed with:
Single prime mover operation or
Two or more prime movers controlled by Woodward load sharing control
systems on an isolated bus
The droop mode is used for speed control as a function of load with:
Single prime mover operation on an infinite bus or
Parallel operation of two or more prime movers
The base load mode provides constant load level operation against a bus with
the load controlled by the 2301D.
The load setting is set by a fixed reference,
or an external analog input,
or external contact control of the reference.
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...