Manual 26247
2301D/2301D-EC Digital Control
Woodward
77
Chapter 6.
Description of Operation
Introduction
This chapter provides an overview of the features and operation of the 2301D
Load Sharing and Speed Control.
The 2301D Load Sharing and Speed Control uses a 32 bit microprocessor for all
control functions. All control adjustments are made with an external computer
that communicates with the control via a serial port. The external computer can
be disconnected from the control during normal operation, to provide security
against tampering.
The speed and load sharing section of these 2301D models monitors and
controls two functions:
Speed
The speed control section keeps the prime mover at the correct speed.
Load Control
The load control section manages the prime mover load based on the load
control mode:
During parallel operation of two or more generators, the load sharing section
senses the load carried by its generator and causes the loads of all
generators in the system to be shared proportionally.
During parallel operation of two or more generator or a generator paralleled
against an infinite bus the control may be operated in Baseload mode.
During parallel operation of two or more generator or a generator paralleled
against an infinite bus the control may be operated in Droop mode
Speed Control
The Speed Control system as shown in Figure 6-1 consists of:
A device (1) to sense the speed of the prime mover
A frequency sensor to software converter (2)
A speed reference [software] (3) to which the prime mover speed can be
compared
A speed summer/amplifier [software] (4) with an output [software to
hardware] proportional to the amount of fuel or steam required to maintain
the desired speed at any given load
An actuator (5) to position the fuel or steam mechanism of the prime mover
A speed-sensing device, such as a magnetic pickup, senses the speed of the
prime mover, and converts it to an ac signal with a frequency proportional to
prime mover speed. The frequency-to-software receives the ac signal from the
speed sensor and changes it to a digital number representing prime mover rpm.
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...