2301D/2301D-EC Digital Control
Manual 26247
56
Woodward
10 RELAY 2 OFF LEVEL=
dflt = 0.000 (-32000.00, 32000.00)
Enter the level switch OFF setting in engineering units.
(Must be less than the ‘Relay On Level’).
11 RELAY 3 SELECTED AS
(Monitor)
Displays the function selected for terminal 43. This relay is selected in the
configure menu D**DISCRETE OUT OPTIONS**
12 RELAY 3 LEVEL SW (1-6)
dflt = 2 (1, 6)
Select one of the following parameters for discrete output at terminals 43 when it
was selected as a level switch.
1 NOT
USED
2 ACTUAL
SPEED
3 SPEED
REFERENCE
4
START LIMITER SETPOINT
5 ACTUATOR
DEMAND
6
GENERATOR OUT (LOAD SENSOR)
13 RELAY 3 LEVEL SELECT FOR
(Monitor)
Displays the level function selected for terminal 43.
14 RELAY 3 ON LEVEL =
dflt = 0.000 (-32000.00, 32000.00)
Enter the level switch ON setting in engineering units. There is an ON and an
OFF setting for each level switch option. This allows you to program the desired
hysteresis for the function selected.
15 RELAY 3 OFF LEVEL =
dflt = 0.000 (-32000.00, 32000.00)
Enter the level switch OFF setting in engineering units (must be less than the
‘Relay On Level’).
16 RELAY 4 SELECTED AS
(Monitor)
Displays the function selected for terminal 44. This relay is selected in the
configure menu - D**DISCRETE OUT OPTIONS**
17 RELAY 4 LEVEL SW (1-6)
dflt = 1 (1, 6)
Select one of the following parameters for discrete output at terminals 44 when it
was selected as a level switch.
1 NOT
USED
2 ACTUAL
SPEED
3 SPEED
REFERENCE
4
START LIMITER SETPOINT
5 ACTUATOR
DEMAND
6
GENERATOR OUT (LOAD SENSOR)
18 RELAY 4 LEVEL SELECT FOR
(Monitor)
Displays the level function selected for terminal 44
19 RELAY 4 ON LEVEL =
dflt = 0.000 (-32000.00, 32000.00)
Enter the level switch ON setting in engineering units. There is an ON and an
OFF setting for each level switch option. This allows the user to program the
desired hysteresis for the function selected.
20 RELAY 4 OFF LEVEL =
dflt = 0.000 (-32000.00, 32000.00)
Enter the level switch OFF setting in engineering units.
(Must be less than the ‘Relay On Level’).
21 BREAKER OPEN TIME (SEC)
dflt = 1.000 (0.80, 60.00)
Sets the time the automatic circuit breaker command time will change states
(depending on the configuration of CB Open Relay Normally Energized).
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...