2301D/2301D-EC Digital Control
Manual 26247
52
Woodward
13 MAP DELAY TIME CONTACT
dflt = 0.500 ( 0.00, 30.00)
When the maximum air pressure limit is within the near fuel limit range for longer
then this delay time an overload contact is activated.
14 MAP OVERLOAD PULS TIME
dflt = 0.500 (0.00, 100.00)
This is the time for the overload contact to be active. In Configure Menu
C**Discrete Out Options** a discrete output can be setup at parameter 8
(Overload Contact).
N**LOAD SETTINGS**
The Load Setting section is the set-up of the generator load control parameters.
01 LOAD DROOP PERCENT
dflt = 5.000 (0.00, 12.00)
is the percentage of rated speed the speed reference will droop when the
generator load is increased to maximum load. Set to desired droop percent.
02 LOAD LEVEL VOLTAGE
dflt = 6.000 (0.10, 9.00)
Sets the voltage level of the load.
03 LOAD SHARE GAIN
dflt = 1.000 (0.01, 10.00)
Sets the load sharing gain. A too-high gain will result in unstable load sharing
between the units.
04 BASE LOAD MINIMUM (KW)
dflt = 20.000 (10.00, 30000.00)
The minimum value the base load reference will ramp to when the external lower
switch at terminal 36 is closed.
05 BASE LOAD REFERENCE (KW)
dflt = 50.000 (0.00, 30000.00)
Enter the internal Baseload set point. This sets the initial internal set point of the
Baseload Reference Ramp when the Load Control enters Base Load mode.
06 BASE LOAD MAXIMUM (KW)
dflt = 110.000 (10.00, 30000.00)
The maximum value the base load reference will ramp to when the external raise
switch at terminal 35 is closed.
07 BASELOAD RAISE TIME (SEC)
dflt = 60.000 (1.00, 600.00)
The time for the reference to ramp from baseload minimum to baseload load
maximum values entered above.
08 BASELOAD LOWER TIME (SEC)
dflt = 60.000 (1.00, 600.00)
The time for the reference to ramp from baseload maximum to baseload load
minimum values entered above.
09 UNLOAD TRIP LEVEL (KW)
dflt = 5.000 (0.00, 30000.00)
Enter the unload trip level set point. This sets the load level that the unit unloads
to following an Unload command. When the Load switch is opened to unload, the
generator unloads to this KW value. The Discrete output 4 will then change state
momentarily to give a breaker open command.
10 LOADING RATE (KW/SEC)
dflt = 20.000 (1.00, 600.00)
Enter the loading rate. This sets the rate at which the Load Ramp will increase
for soft loading.
11 UNLOADING RATE (KW/SEC)
dflt = 20.000 (1.00, 600.00)
Enter the unloading rate. This sets the rate at which the Load Ramp will
decrease for soft unloading.
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...