2301D/2301D-EC Digital Control
Manual 26247
92
Woodward
Control Test and Calibration
General
Do the following checks on the 2301D control. Then verify the functioning of set
points and adjustments.
1. Connect a computer to the communication port. Start Watch Window HMI
software in accordance with the instructions in Chapter 4. Verify that correct
voltage and polarity are applied to the control.
2. Verify the controller ID on the 2301D Standard PC Interface by clicking
“Control” then “Properties”. The Application ID message (part number with
the revision level [new, A, etc]) should appear.
3. Select the 1st Dynamics Menu. Verify that all set points are as recorded
during installation. Repeat for the other menus. If any differences are found,
change the set point(s) to the correct value. Click the “SAVE VALUES” icon
on the Tool bar. Remove power from the control for at least 10 seconds.
Verify correct values were retained during power down. Failure indicates the
control has failed and should be replaced.
Discrete Inputs
Do the following test to verify the function of the discrete inputs. Do NOT do this
test with the engine running.
1. Repeat this step for all discrete inputs. Close the appropriate input. The
status in DISPLAY DIGITAL I/O should switch from OPEN to CLOSED. If the
value does not change when the contact is closed, the control has failed and
should be replaced.
Discrete Outputs
To Verify operation of the Discrete Outputs, go to the RELAY AND ANOUT
TESTS sheet. With the engine shut down, enable the manual relay driver test.
Open another inspector sheet, select DISPLAY DIGITAL I/O, and monitor the
discrete outputs DO1 – DO4. From the relay test procedure, each discrete output
may be activated and its operation verified. If the output is activated, the same
voltage as applied at terminal 39 and 40 should be measured between terminal
39 and the appropriate output terminal (41–44). Testing of the internal CB Aux
relay may be done by observing the green LED near terminal 9 and 10, or
hearing an audible ‘click’. The manual relay test must be disabled (status “test
off”) or the control will hold the actuator current to minimum.
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...