2301D/2301D-EC Digital Control
Manual 26247
32
Woodward
Parameters 11 thru 14 are only applicable for the 2301D-EC with Modbus (see
Chapter 8, Communications):
11 = MODBUS RELAY #1
12 = MODBUS RELAY #2
13 = MODBUS RELAY #3
14 = MODBUS RELAY #4
04 RELAY 1 SELECTED FOR
(monitor)
Displays the relay function for terminal 41.
05 RELAY 2 ENERGIZES (1-14)
dflt = 3 (1, 14)
Select one of the following parameters for discrete output at terminal 42 (same
as parameters in 03 RELAY 1 ENERGIZES).
06 RELAY 2 SELECTED FOR
(monitor)
Displays the relay function for terminal 42.
07 RELAY 3 ENERGIZES (1-14)
dflt = 9 (1, 14)
Select one of the following parameters for discrete output at terminal 43 (same
as parameters in 03 RELAY 1 ENERGIZES).
08 RELAY 3 SELECTED FOR
(monitor)
Displays the relay function for terminal 43.
09 RELAY 4 ENERGIZES (1-14)
dflt = 7 (1, 14)
Select one of the following parameters for discrete output at terminal 44 (same
as parameters in 03 RELAY 1 ENERGIZES).
10 RELAY 4 SELECTED FOR
(monitor)
Displays the relay function for terminal 44.
11 CB OPEN RELAY NORM ENGZD
dflt = FALSE (FALSE, TRUE)
When set TRUE sets the circuit breaker open relay to normally closed.
D**ANALOG INPUT OPTIONS**
01 CONFIGURATION ERROR ?
(monitor)
Set TRUE when both analog inputs are configured the same. You must configure
both analog inputs different from each other.
02 SEL AI #1 FUNCTION (1-6)
dflt = 4 (1, 6)
Selects the function for the analog input:
1 = NOT USED
2 = REMOTE SPEED SETPOINT
3 = BASELOAD SETPOINT
4 = SYNC INPUT
5 = AUXILIARY SPEED SETPOINT
6 = MANIFOLD AIR PRESSURE LIMITER INPUT
03 DISPLAY AI #1 FUNCTION
(monitor)
Displays the function for analog input #1.
04 SEL AI #1 TYPE (1-4)
dflt = 4 (1, 4)
Sets the type of input used:
1 = 4-20 mA
2 = 0-5 Volt
3 = ±2.5 Volt
4 = 1-5 Volt
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...