Manual 26247
2301D/2301D-EC Digital Control
Woodward
33
05 DISPLAY AI #1 TYPE
(monitor)
Displays the type of input for analog input #1.
06 USE INPUT #1 FAIL TRIP
dflt = FALSE (FALSE, TRUE)
When set TRUE a failure of the input signal gives a major alarm, which
shutdowns the engine. When set FALSE only an alarm is given, and the engine
is not stopped.
07 SEL AI #2 FUNCTION (1-6)
dflt = 3 (1, 6)
Selects the function for the analog input:
1 = NOT USED
2 = REMOTE SPEED SETPOINT
3 = BASELOAD SETPOINT
4 = SYNC INPUT
5 = AUXILIARY SPEED SETPOINT
6 = MANIFOLD AIR PRESSURE LIMITER INPUT
08 DISPLAY AI #2 FUNCTION
(monitor)
Displays the function for analog input #2.
09 SEL AI #2 TYPE (1-4)
dflt = 4 (1, 4)
Sets the type of input used:
1 = 4-20 mA
2 = 0-5 Volt
3 = ±2.5 Volt
4 = 1-5 Volt
10 DISPLAY AI #2 TYPE
(monitor)
Displays the type of input for analog input #2.
11 USE INPUT #2 FAIL TRIP
dflt = FALSE (FALSE, TRUE)
When set TRUE a failure of the input signal gives a major alarm, which
shutdowns the engine. When set FALSE only an alarm is given, and the engine
is not stopped.
E**ACTUATOR OUT OPTIONS**
01 ACTUATOR OUT TYPE (1-3)
dflt = 1 (1, 3)
Selects the current range of the actuator used:
1 = 0-200 mA
2 = 4-20 mA
3 = 0-20 mA
02 DISPLAY ACTUATOR TYPE
(monitor)
Displays what current range is set for the actuator.
03 REVERSE ACTING ACTUATOR
dflt = FALSE (FALSE, TRUE)
Set to TRUE for reverse-acting actuators and FALSE for forward-acting
actuators. Forward-acting actuators require current increase to increase fuel.
Reverse-acting actuators require current decrease to increase fuel (reverse-
acting actuators should always incorporate a mechanical ballhead backup
governor, such as the Woodward EGB).
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...