Manual 26247
2301D/2301D-EC Digital Control
Woodward
9
Chapter 2.
Installation
Introduction
This chapter contains general installation instructions for the 2301D control.
Power requirements, environmental precautions, and location considerations are
included to determine the best location for the control. Additional information
includes unpacking instructions, electrical connections, and an installation check-
out procedure.
Unpacking
Before handling the control, read Chapter 2 “Electrostatic Discharge Awareness”.
Be careful when unpacking the electronic control. Check the control for signs of
damage such as bent or dented panels, scratches, and loose or broken parts. If
any damage is found, immediately notify the shipper.
Power Requirements
The 2301D control requires a voltage source of 18 to 40 Vdc, with a current
capacity of at least 900 mA for operating power. If a battery is used for operating
power, an alternator or other battery charging device is necessary to maintain a
stable supply voltage.
To prevent damage to the control, make sure that the alternator or
other battery-charging device is turned off or disconnected before
disconnecting the battery from the control.
Location Considerations
This product is intended for installation in a “closed electrical operating area” or in
an enclosed industrial control cabinet. Consider these requirements when
selecting the mounting location:
Adequate ventilation for cooling
Space for servicing and repair
Protection from direct exposure to water or to a condensation-prone
environment
Protection from high-voltage or high-current devices, or devices which
produce electromagnetic interference
Avoidance of vibration
Selection of a location that will provide an operating temperature range of
–40 to +70 °C (–40 to +158 °F)
The control must NOT be mounted on the engine.
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...