2301D/2301D-EC Digital Control
Manual 26247
30
Woodward
12 OVERSPEED SETTING
dflt = 2000.00 (0.00, 4000)
The maximum speed limit. The 2301D initiates a shutdown when the engine
speed reaches this level.
13 RST TO RATED AT CB CLOSE
dflt = TRUE (TRUE, FALSE)
This resets the speed bias after the circuit breaker is closed and the speed
setting returns to rated.
14 RST TO RATED INSTANT
dflt = TRUE (TRUE, FALSE)
Used to return the engine immediately back to rated.
15 GRID FREQ IS 50 HZ
dflt = FALSE (TRUE, FALSE)
If set FALSE 60 Hz is selected.
16 RSE/LWR STOP IDL/RTD RMP
dflt = TRUE (TRUE, FALSE)
If set TRUE the raise and lower inputs are active during ramping from idle to
rated. When FALSE the raise and lower inputs are disabled until rated speed is
reached.
17 ENABLE AUTO IDLE/RATED
dflt = FALSE (TRUE, FALSE)
An automatic idle to rated switch which activates rated after idle is reached and a
certain time has expired. Tunable in service mode.
B**DISCRETE IN OPTIONS**
01 SEL DI B FUNCTION (1-8)
dflt = 2 (1, 8)
Used to select the function for digital input 2 (B) terminal 32.
1 Not
used
2
Failed speed override (default)
3 Reset
4 Select
2
nd
dynamics
5 Shutdown
external
On a forward-acting actuator, the fuel demand will go to 0%. On a
reverse-acting actuator, the fuel demand will go to 100%, and will
cause the mechanical governor to take over.
6 Idle/rated
switch
7
Generator Breaker (52G) Isoch
8
Use Modbus (for 2301D-EC with Modbus)
02 DISPLAY DI B FUNCTION
(monitor)
Shows the function of input B.
03 SEL DI C FUNCTION (1-8)
dflt = 6 (1, 8)
Used to select the function for digital input 3 (C) terminal 33.
1 Not
used
2
Failed speed override
3 Reset
4 Select
2
nd
dynamics
5 Shutdown
external
On a forward-acting actuator, the fuel demand will go to 0%. On a
reverse-acting actuator, the fuel demand will go to 100%, and will
cause the mechanical governor to take over.
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...