Manual 26247
2301D/2301D-EC Digital Control
Woodward
111
SERVICE MENU
PROGRAMMED
VALUE
DEFAULT
VALUE
TUNABLE RANGE
MIN.
MAX.
13 INTERNAL CB AUX RELAY
Monitor
F**DISPLAY ANALOG I/O**
01 SPEED SENSOR INPUT (RPM)
Monitor
02 LOAD SENSOR INPUT (KW)
(Monitor
03 ANIN #1, INPUT TYPE:
(Monitor
04 ANIN #1 (UNITS)
(Monitor
05 ANIN #2 INPUT TYPE:
(Monitor
06 ANIN #2 (UNITS)
(Monitor
07 LOAD SHARING LINES (VDC)
Monitor
08 LOAD SHARING BIAS SIG(%)
Monitor
09 ACTUATOR CURRENT (mA)
Monitor
10 ANALOG OUT 1 (%)
Monitor
11 LOAD SIGNAL OUT (Vdc)
Monitor
G**SPEED SETTINGS**
01 START SPEED (RPM)
400.000
1.00
2100.00
02 RAISE SPEED LIMIT (RPM)
1000.000
0.00
4000.00
03 LOWER SPEED LIMIT (RPM)
800.000
0.00
4000.00
04 IDLE SPEED (RPM)
600.000
0.00
4000.00
05 ACCEL RAMP TIME (SEC)
20.000
1.00
300.00
06 DECEL RAMP TIME (SEC)
20.000
1.00
300.00
07 SPEED TRIM INC TIME(SEC)
30.000
1.00
300.00
08 SPEED TRIM DEC TIME(SEC)
30.000
1.00
300.00
09 ACT OUT AT RATED NO LOAD
20.000
0.00
100.00
10 ACT OUT RATED FULL LOAD
80.000
0.00
100.00
11 ACT POS DROOP (%)
0.000
0.00
100.00
12 IDLE DROOP BREAKPOINT
20.000
0.50
100.00
13 IDLE DROOP (%)
0.000
0.00
100.00
14 DELAY TIME IDLE TO RATED
5.000
0.00
600.00
H**DYNAMICS #1**
01 PROP GAIN 1
2.000
0.01
100.00
02 RESET 1
2.000
0.01
100.00
03 ACTUATOR COMPENSATION 1
12.000
0.01
100.00
04 WINDOW WIDTH 1 (RPM)
60.000
1.00
200.00
05 GAIN RATIO 1
1.000
1.00
10.00
06 SPEED FILTER FREQ 1 (HZ)
20.000
4.00
20.00
07 BUMP ACT TRIG (T THEN F)
FALSE
TRUE
FALSE
I**DYNAMICS #2**
01 ENABLE DYNAMICS 2 w/CB
FALSE
TRUE
FALSE
02 DELAY DYN 2 ENABLE (SEC)
0.00
0.00
20.00
03 DELAY DYN 1 ENABLE (SEC)
0.00
0.00
20.00
04 PROP GAIN 2
4.000
0.01
100.00
05 RESET 2
2.000
0.01
100.00
06 ACTUATOR COMPENSATION 2
12.000
0.01
100.00
07 WINDOW WIDTH 2 (RPM)
60.000
1.00
200.00
08 GAIN RATIO 2
1.000
1.00
10.00
09 SPEED FILTER FREQ 2 (HZ)
20.000
4.00
20.00
10 BUMP ACT TRIG (T THEN F)
FALSE
TRUE
FALSE
J**DYNAMICS #1, 5 PT GAIN**
01 BREAKPOINT 1A (%LD or RPM)
99.600
0.01
5000.00
02 GAIN @BREAKPOINT 1A
4.0
0.01
100.00
03 BREAKPOINT 1B (%LD or RPM)
99.700
0.01
5000.00
04 GAIN @BREAKPOINT 1B
4.0
0.01
100.00
05 BREAKPOINT 1C (%LD or RPM)
99.800
0.01
5000.00
06 GAIN @BREAKPOINT 1C
4.0
0.01
100.00
07 BREAKPOINT 1D (%LD or RPM)
99.900
0.01
5000.00
08 GAIN @BREAKPOINT 1D
4.0
0.01
100.00
09 BREAKPOINT 1E (%LD or RPM)
100.00
0.01
5000.00
10 GAIN @BREAKPOINT 1E
4.0
0.01
100.00
11 RESET 1
2.000
0.01
100.00
12 ACT COMPENSATION
12.000
0.01
100.00
13 WINDOW WIDTH 1 (RPM)
60.000
1.00
200.00
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...