Manual 26247
2301D/2301D-EC Digital Control
Woodward
53
12 ENABLE FAST LOAD RATE
dflt = FALSE (TRUE, FALSE)
Set to TRUE if the function to activate a faster loading ramp rate than the
LOADING RATE entered above when the system load level is high.
13 FAST RAMP ENABLE LOAD (%)
dflt = 80.000 (1.00, 110.00)
When the system load, as measured through the load sharing lines, is
determined to by above this percentage the soft load ramp rate will switch to a
faster rate to allow this oncoming unit to pick up it share of the load faster.
14 FAST RAMP RATE (KW/SEC)
dflt = 60.000 (1.00, 600.00)
Enter the loading rate at which the load will increase when the system load is
above the percentage entered above.
O**ACTUATOR BUMP SETUP**
01 BUMP ENABLED
dflt = FALSE (TRUE, FALSE)
Set to TRUE to enable the actuator bump for 60 minutes. Set to FALSE to
disable this function. When this prompt is set FALSE, the Actuator Bump tunable
in the Dynamics sections described above is disabled.
02 ACT BUMP LEVEL (%FD)
dflt = 1.000 (0.00, 25.00)
This is the % fuel demand for the desired bump level.
03 ACT BUMP DURATION (SEC)
dflt = 0.110 ( 0.08, 2.00)
The desired bump duration in seconds.
04 BUMP ACT TRIGGER (T THEN F)
dflt = FALSE ( TRUE, FALSE)
Allows you to test your dynamic settings by temporarily applying a decrease fuel
demand transient to stimulate a control response. To initiate an actuator bump,
toggle Bump Act to TRUE then back to FALSE while the engine is operating in a
normal steady state loaded or unloaded condition.
P**ANALOG INPUTS SETTINGS**
This group of Service settings set the parameters of the two analog inputs at
terminals 19 through 24.
01 AI 1 CONFIGURED FOR:
(monitor)
This will display the function Analog Input #1 at terminal 19–21 was set for in the
Configure mode.
02 AI 2 CONFIGURED FOR:
(monitor)
This will display the function Analog Input #2 at terminal 22–24 was set for in the
Configure mode.
03 SPEED w/ RMT IN@MIN(RPM)
dflt = 800.000 (0.00, 4000.00)
Sets the speed reference value when the remote reference input is at the low
value for the selected range. This value may be less than or greater than the
value entered when the input is at maximum.
04 SPEED w/ RMT IN@MAX(RPM)
dflt = 1000.000 (0.00, 4000.00)
Sets the speed reference value when the remote reference input is at the
maximum value for the selected range.
Содержание 2301D
Страница 12: ...2301D 2301D EC Digital Control Manual 26247 4 Woodward Figure 1 1a 2301D Outline Drawing Ordinary Locations ...
Страница 13: ...Manual 26247 2301D 2301D EC Digital Control Woodward 5 Figure 1 1b 2301D Outline Drawing Hazardous Locations ...
Страница 14: ...2301D 2301D EC Digital Control Manual 26247 6 Woodward Figure 1 2a 2301D Plant Wiring Diagram sheet 1 ...
Страница 16: ...2301D 2301D EC Digital Control Manual 26247 8 Woodward Figure 1 2c 2301D Plant Wiring Diagram notes ...
Страница 51: ...Manual 26247 2301D 2301D EC Digital Control Woodward 43 Figure 3 4 Typical Transient Response Curves ...
Страница 127: ...Manual 26247 2301D 2301D EC Digital Control Woodward 119 ...
Страница 129: ...Declarations ...